• Plot No. W-35/B, Additional MIDC Area, MIDC Ambad, Nashik, Maharashtra - 422 010.
  • Call Us: (0253)-6628079, 9373910599
  • info@gbcontrols.com

HT APFC Relay (3 Phases, 3 CT)

Thristor/Contactor Switched APFC System

HT Automatic Power Factor Correction Controller
(3Phases, 3CT / 2Phases, 2CT / 1Phase, 1CT)

An intelligent high speed DSP + Microprocessor Based device to measure, calculate, display and store all electrical network parameters. Voltage & Current Feedback is achieved through HT CT’s & PT’s.

In built Intelligent Multi Method Switching (MMS) Algorithm enables user to get close control on network reactive power requirement. Multi Method Switching (MMS) Algorithm allows user to set different target power factor for Diesel Generators and Windmill Stations. A built in self test facility provided for checking the operation of the relay without external load. The controller functions even at low operating loads with great accuracy.

GB Control’s APFC controller find usage and applications in all segments of industry viz Automobile factories, Cement Plants, Chemical & Fertilizer Plants, Metal Industries Electrical Distribution Network(Utilities) etc.

The other built in features viz Over Voltage Protection, Low Voltage Protection, Under Load Protection, Over Load Protection High Temperature, Storage facility and Communication available through GSM,RS232,RS485 etc. provides nonstop operation of APFC System.

Thristor/Contactor Switched APFC System

Thristor/Contactor Switched APFC System

Features:

  • Accuracy Class I
  • Certified from NABL accredited Laboratory
  • DATA memory-45 days on hourly basis
  • 2 / 4 Line LCD Display with backlit
  • Computerized Test & Calibration Report
  • IP-54 Degree
  • Highly Sensitive
  • Intelligent Multi Method Switching Algorithm
  • Four Quadrant Measurement
  • Communication port RS-232/485
  • Plug & Play Operation
  • Plug in Terminal
  • Payment Lock Facility

Model No. Size

GB/HT/3L/CSR-04

GB/HT/3L/CSR-06

GB/HT/3L/CSR-08

Size (mm)

144X144X80

Accuracy

Class-1

Steps Outputs

04 Nos.

06 Nos.

08 Nos.

Operating Input Voltage

110 To 270 Volts AC

Measuring Voltage

110 Volts AC, 3 Phase, 4 Wire

CT Input

5VA, In/1A , In/5A

Output Signal

230V,5A, Potential free Relay

Display Type

16X2 Line LCD Display

LED Indications

Step ON, Discharge, Fault

Protections/Fault

HV, LV, UL, OL, HIGH TEMP, OC, H_THD etc.

Programming Parameters

Target Power Factor, CT Ratio, Response Time, Discharge Time, Connected Steps, Steps Rating, Fix Step, Fault Limits, Fault Enable/Disable, etc.

RS-232 / 485

Provided